Home > Products

110kV-500kV Full-series Power Transformers

What sets Neel’s 110kV–500kV transformers apart is how we combine precision engineering, a full suite of international certifications, and agile design capabilities. That combination lets us deliver site-specific power solutions that perform reliably across the world’s most diverse grid networks.

Product Introduction

Our 110kV to 500kV transformers combine precision manufacturing, global certifications, and agile customisation to give you reliable, site-adapted power for smart grids, renewables, rail, and transmission applications.

In the workshop, JOERG shear lines hold silicon steel burrs below 0.02 mm, and we use Japanese grain-oriented high-permeability steel to keep core losses and noise low from the very first cut. High-voltage windings are wound on automatic machines; low-voltage foil windings get automatic foil winding with argon-shielded welding – that ensures low resistance and high conductivity. We also hold patents on winding processing devices and methods, which adapt to different winding sizes and even clean themselves during production.

Every transformer type has passed full type tests – including short-circuit withstand – at China’s national transformer quality supervision centre. Beyond that, we carry KEMA, CESI, ASTA, and CE certifications. So whether your market follows IEC, GOST, or ANSI, our test reports already satisfy local grid entry requirements. That saves you the usual weeks of extra paperwork, translation, and surprise re-testing fees.

We’ve got nearly 200 technical engineers on hand, ready to respond to your specific challenges. Need insulation adjustments for a high-altitude mine in South America? Wide-range tap changing for an ageing grid in Central Asia? Special oil formulations and seals for extreme cold in Russia? We’ll design it, produce multilingual documentation, and help you navigate local certification procedures – all as part of the package.

Technical Parameters

1. 110kV Power Transformer

Parameters

Value

Rated Capacity (MVA)

6.3 - 180

Rated Voltage Ratio

Two-winding: 110 / 10.5 kV, 110 / 11 kV, 110 / 37 kV, etc.

Three-winding: 110 / 37 / 10.5 kV, 110 / 38.5 / 11 kV, etc.

Tap Changer Range

(110 ±8×1.25%) or (110 ±2×2.5%)

Short-circuit Impedance (%)

10.5 - 12.5

No-load Loss (kW)

20 - 120

Load Loss (kW)

90 - 550

Vector Group

YNd11, YNyn0d11, YNyn0y10

Cooling Method

ONAN,  ONAF

 

2. 220kV Power Transformer

Parameters

Value

Rated Capacity (MVA)

40 - 480

Rated Voltage Ratio

220 / 121 / 11 kV, 220 / 121 / 38.5 kV, etc.

Tap Changer Range

220 ±8×1.25%

Short-circuit Impedance (%)

12 - 16

No-load Loss (kW)

100 - 250

Load Loss (kW)

450 - 900

Vector Group

YNyn0d11, YNyn0y10

Cooling Method

ONAN/ONAF, OFAF

 

3. 330kV Power Transformer

Parameters

Value

Rated Capacity (MVA)

90 - 500

Rated Voltage Ratio

363 / 121 kV, 363 / 20 kV, etc.

Tap Changer Range

330 ± 8×1.25%

Short-circuit Impedance (%)

14 - 18

No-load Loss (kW)

150 - 350

Load Loss (kW)

600 - 1200

Vector Group

YNd11, YNyn0d11

Cooling Method

 OFAF, ODAF

 

4. 500kV Power Transformer

Parameters

Value

Rated Capacity (MVA)

250 - 1000

Rated Voltage Ratio

525 / 242 / 34.5 kV, 530 / 27 kV

Tap Changer Range

500 ± 2×2.5%

Short-circuit Impedance (%)

18 - 22

No-load Loss (kW)

250 - 450

Load Loss (kW)

1200 - 2500

Vector Group

 YNyn0d11, YNd11

Cooling Method

OFAF, ODAF